INTELLIGENT GAS RELEASE PANEL
This panel controls the automatic release of a fire extinguishant. Two separate fire alarm signals are required to initiate the release sequence. The automatic release may be switched to manual release mode via a keyswitch at the panel. A yellow manual release mechanism is housed on the panel facia. Visual alarm, audible alarm and gas discharge outputs are monitored for short and open circuit fault. The two fire alarm inputs are also monitored. These circuits are provided with lightning protection. Repeater panels can be connected via the RS485 communications port. The first fire signal received will activate a 24 VDC bell contact, the second fire signal will activate the two initiate outputs and after a 30 or 60 second delay, the discharge output. This version gas panel has been fitted with an intelligent interface unit (T331-04).
More Information +
The panel is thus controlled by an addressable fire control panel. Two separate fire alarm signals must be received from the addressable fire panel to initiate the extinguishant release. The interface unit will also relay important status conditions to the fire panel. These include Common Fault, Release Initiated, Release Discharged and Auto/Manual mode. A “Door Contact” status is an additional safety feature this gas panel provides. If enabled this feature will activate an alarm contact when a) the panel is switched to automatic release mode but a monitored door contact is open, or b) when the panel is switched to manual mode but the monitored door contact is closed. Personnel entering a protected area should not leave the panel in automatic release mode and personnel leaving the area should not leave the panel in the manual release mode! An additional addressable switch monitor unit will be required to convey the “Door Contact” status to the addressable fire control panel. The panel housing is manufactured in extremely durable 1.2mm thick powder coated sheet metal.

Specifications:

Operating voltage 24v DC
Quiescent current @ 24 VDC 25 mA
Extinguishant release contacts 24V, 5 Amp for 3 seconds or 5 minutes and potential
Initiate release outputs 2x 24VDC 2 Amp and 2 x potential free change over
Bell output 1x 24VDC 2 Amp
Repeater output RS 485 Modbus
Dimensions - (H x W x D) 180mm x 250mm x 86mm
Weight 1. 7 kg
STATEX AUTOMATIC FIRE SUPPRESSION SYSTEM
Upon detection of a fire, Stat-X generators can be activated either manually or automatically from a suitable listed releasing device. Upon activation, the generators produce an exceptionally effective, ultra-fine, potassium based aerosol. Stat-X aerosol generators are very cost effective to install and maintain - as they do not require the pressure vessels, piping or expensive installation. Space and weight requirements are minimal. The Stat-X generator’s effectiveness is a function of its patented design, aerosol composition, and ultra-fine particle size. Fire suppression is rapidly achieved through interference between the ultra-fine aerosol particulate and the flame's free radicals - terminating propagation of the fire. Stat-X aerosol generators are virtually maintenance free and have a service life of over 10 years. This, coupled to their very low installation cost, makes them an extremely cost effective fire protection solution.
More Information +
Due to their fast response time, low fire extinguishing concentration, and environmental safety, Stat-X fire suppression systems may be used in critical applications across a wide range of industries. Aerosol generators are currently protecting and are suitable for use in; Telecommunications facilities ; Process control rooms ; PABX rooms ;High value mobile equipment; Cellular sites and relay towers; Data processing facilities ; Flammable liquid storage areas; Turbine and generator enclosures; Marine engine rooms and machinery spaces; Power plants ; Small boats; General industrial hazards.

Specifications:

CHARGE 2v DC MASS VARIOUS PROPELLANT NILL
EXTINGUISHANT STATEX WORKING PRESSURE N/A FIRE RATING SUSPPRESSION SYSTEM MAX 80m2
APPROVALS UL, ULC, CSIRO, ECB TEST PRESSURE N/A FOR USE ON FIRES CLASSED A, B, C